SAMSON Banner
      
Best Resolution 1024x768
 
 
 
 


LOCAL AREA NETWORK (LAN) CABLE

Category 5 Enhanced Unshielded & Foiled Twisted Pair

CHARACTERISTICS Listing & Verified E208378

  • Temperature rating : -20˚C to +75˚C
  • Rated voltage : 300V
  • Applicable Standard : UL444, TIA/EIA568B.2

PRODUCT DESCRIPTION

  • 24 AWG solid plain annealed copper conductors.
  • Color code PE insulated, twisted pair.
  • Drain wire
  • Al. Foil for shielding.
  • Rip cord easy for stripping.
  • Sheath : PVC
  • Available with Jelly Fill and Armored, PE or LSHF Sheath.

APPLICATION

  • Horizontal Distribution.

GENERAL CHARACTERISTICS

Characteristic
Impedance

Max. DC resistance

Max. Resistance Unbalance

Max. Mutual Capacitance

Max.
Capacitance Unbalance

Nominal Velocity
Ratio

100±15 Ω

9.38 Ω/100m

5 %

5.6 nF/100m

330 pF/100m

65%

CABLE CONSTRUCTION

Diagram

Model No.

No. of Pairs

Conductor

Insulation Nom. Dia. (mm)

Insulation Colour

Sheath Nom. Dia. (mm)

AWG

No./mm

CAT5EUTP/2P

2

24

1/0.517

0.92

Colour Chart 1

3.1X5.1

CAT5EUTP/4P

4

24

1/0.517

0.92

Colour Chart 1

5.4

CAT5FTP/4P

4

24

1/0.542

1.025

Colour Chart 1

6.5

ELECTRICAL PERFORMANCE

Frequency
(MHz)

Max. Attenuation
(dB/100m)

Min.
RL
(dB/100m)

Min.
SRL
(dB/100m)

Min.
Worst Pair N.E.X.T. (dB/100m)

Min.
Worst Pair PS N.E.X.T. (dB/100)

Min.
Worst Pair ELFEXT (dB/100)

Min.
Worst Pair
PS ELFEXT (dB/100m)

Max.
PD
(ns/100m)

Max.
PDS
(ns/100m)

.772

***

19.4

***

67.0

64.0

66.0

63.0

***

45

1

2

20.0

23

65.3

62.3

63.8

60.8

570

45

4

4.1

23.0

23

56.3

53.3

51.76

48.76

***

45

8

5.8

24.5

23

51.8

48.8

45.74

42.74

***

45

10

6.5

25.0

23

50.3

47.3

43.80

40.80

545

45

16

8.2

25.0

23

47.3

44.4

39.72

36.72

***

45

20

9.3

25.0

23

45.8

42.8

37.78

34.78

***

45

25

10.3

24.3

22

44.3

41.3

35.84

32.84

***

45

31.25

11.7

23.6

21

42.9

39.9

33.90

30.90

***

45

62.5

17

21.5

18

36.4

35.4

27.88

24.88

***

45

100

22

20.1

16

35.3

32.3

23.80

20.80

538

45

  • All value are worst case. Test were set up in accordance with TA/EIA 568 B.2. The value shown are typical and subject to change.